No. Type Functionality
1 UTXvZRP UTXvZRP series 3 UTXvZRP series 2
Universal distance, differential, overcurrent and earth fault protection relay 37, 37BC, 23/26, 81U, 81O,
21Z/21ZN, 21GC, 21FL, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 68, 21SOTF/50SOTF, 94,87LP, 85-21/85-87LP/77/68, 64.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF, 62.
21Z/21ZN, 21GC, 21FL, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 68, 21SOTF/50SOTF, 94,87LP, 85-21/85-87LP/77/68, 64.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF, 62.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus.
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus.
2 UTXvZ UTXvZ series 3 UTXvZ series 2
Universal distance, overcurrent and earth fault protection relay 37, 37BC, 23/26, 81U, 81O,
21Z/21ZN, 21GC, 21FL, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 21SOTF/50SOTF, 94, 68, 62, 85-21/77/68, 64.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF.
21Z/21ZN, 21GC, 21FL, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 21SOTF/50SOTF, 94, 68, 62, 85-21/77/68, 64.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS,DiffChannel TRbus.
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS,DiffChannel TRbus.
3 UTXvRP UTXvRP series 3 UTXvRP series 2
Universal differential, overcurrent and earth fault protection relay 37, 37BC, 23/26, 81U, 81O,
21GC, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 21SOTF/50SOTF, 62, 87LP,
85-87LP/77/68, 64.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF.
21GC, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 21SOTF/50SOTF, 62, 87LP,
85-87LP/77/68, 64.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus.
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus.
4 UTXvD UTXvD series 3 UTXvD series 2
Universal overcurrent and earth fault protection relay 37, 37BC, 23/26, 81U, 81O,
21GC, 25, 50/51/67, 59, 27, 49,32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 62, 64, 21SOTF/50SOTF.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF.
21GC, 25, 50/51/67, 59, 27, 49,32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 62, 64, 21SOTF/50SOTF.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS,DiffChannel TRbus.
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS,DiffChannel TRbus.
5 UTXvS UTXvS series 3 UTXvS series 2
Universal earth fault protection relay 37, 37BC, 23/26, 81U, 81O,
21GC, 49, 32, 46, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 62, 64, 21SOTF/50SOTF.
HMI, DFR, SER, PMU, CLK, TCM, LGC, VTFF.
21GC, 49, 32, 46, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 62, 64, 21SOTF/50SOTF.
HMI, DFR, SER, PMU, CLK, TCM, LGC, VTFF.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS,DiffChannel TRbus.
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS,DiffChannel TRbus.
6 UTXvTR UTXvTR series 3 UTXvTR series 2
Universal differential power transformer protection relay 23/26,
87T, 50/51/67, 50H(2), 50H(5), 50BF, 74, 62.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC.
87T, 50/51/67, 50H(2), 50H(5), 50BF, 74, 62.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS.
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS.
7 UTXvL UTXvL series 3 UTXvL series 2
Universal protection relay for a line with the neutral point in any configuration. 37, 25, 37BC, 23/26, 81U, 81O,
50/51/67, 59, 27, 49, 32, 90Q, 41N, 90C, 46, 47, 50N/51N, 59N, 67N, 21YN, 21YNR, 64G,50H(2), 50BF, 81U/81O, 79-81O, 79, 74, 50SOTF, 94, 68, 62, 64.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF.
50/51/67, 59, 27, 49, 32, 90Q, 41N, 90C, 46, 47, 50N/51N, 59N, 67N, 21YN, 21YNR, 64G,50H(2), 50BF, 81U/81O, 79-81O, 79, 74, 50SOTF, 94, 68, 62, 64.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS,DiffChannel TRbus.
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS,DiffChannel TRbus.
8 UTXvMSZ+(LRW) UTXvMSZ+(LRW) series 3
Universal busbar protection relay and circuit
-breaker failure protection
50BF, 74, HMI, DFR, SER, PMU, CLK, LGC, MET.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS.
9 UTXvMSZ UTXvMSZ series 3
Universal busbar protection relay 74, HMI, DFR, SER, PMU, CLK, LGC.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS.
10 UTXvLRW UTXvLRW series 3
Universal circuit
-breaker failure protection
50BF, 74, HMI, DFR, SER, PMU, CLK, LGC, MET.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS.
11 UTXvMR UTXvMR series 3
Universal differential protection relay of line with branches 87, 74, HMI, DFR, SER, PMU, CLK, LGC, MET.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS.
12 UTXvP UTXvP series 3 UTXvP series 2
Universal VT bay protection relay 23/26, 81U, 81O,
59, 27, 46, 47, 59N, 81U/81O, 74, 62, 64.
HMI, DFR, SER, PMU, CLK, MET, LGC, VTFF.
59, 27, 46, 47, 59N, 81U/81O, 74, 62, 64.
HMI, DFR, SER, PMU, CLK, MET, LGC, VTFF.
IEC 61850,
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus.
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus.
13 UTXvA UTXvA series 2
Universal autonomous protection relay for HV or MV bay 50/51/67, 59, 27, 32, 90Q, 41N, 90C, 46, 47, 50N/51N, 59N, 67N, 21YN, 21YNR, 64G, 50H(2), 50BF, 81U/81O, 79-81O, 79, 74, 50SOTF, 94, 68, 62, 64.
HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF.
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS.

 

 

 

 

 

 

 

 
 
Relay Test Equipment

Relay Secondary Injection Equipment

 

Kingsine equipment

 

K50 Series Protection Relay Test Set

  • Use reliability is ensured by its AC measurement and waveform recording, and automatic detection is performed after the relay test set start running, which are independently developed by Kingsine Electric Automation Co.Ltd.
  • All-in-one designed Relay Test Set: built-in industrial computer, embedded style Windows CE system, with stable and reliable performance; mouse and keyboard built in panel or external connection available; LCD display; Windows operation interface;
  • Wide Application from old Electromechanic relay to Modern digital protection relay.Suitable working for many world famous brand protection relays.Such as ABB, ALSTOM, SCHNEIDER, SIEMENS, GE, SEL etc;
  • Simultaneous output of 7 voltage and 6 current; amplitude, phase and frequency adjustable independently;
  • Adjusting output precision by software;
  • Self-protection functions, such as voltage short circuit protection, current open circuit, and external source unexpected input, not well grounding etc;
  • Adopt EMC box and have CE approved;
  • Providing 23 pcs function modules of relay protection testing;
  • Interfaces: RJ45 (PC communications), USB (report upload & software upgrade), GPS interface (multi-tester synchronizing working), VGA (projector for training demonstration), PS/2 (keyboard and mouse);
  • Communications protocol for users, and user defines test solutions according to demands;
  • Upright or horizontal design for box, and independent operation even without the testing bench.

 

K10 Series Protection Relay Test Set
  •  Max. 300V AC voltage per phase, and provide independent auxiliary DC power (0~300V adjustable);
  • Simultaneous output of 7 voltage and 6 current; amplitude, phase and frequency adjustable independently;
  • Full function for PC connection test and offline test;
  • Self-protection functions, such as voltage short circuit protection, current open circuit, and external source unexpected input, not well grounding etc.
  • Wide Application from old Electromechanic relay to Modern digital protection relay.Suitable working for many world famous brand protection relays ;Such as ABB, ALSTOM, SCHNEIDER, SIEMENS, GE, SEL etc.
  •   All-in-one designed Relay Test Set: built-in industrial computer, embedded style Windows CE system, with stable and reliable performance; mouse and keyboard built in panel or external connection available; LCD display; Windows operation interface;
  • Adopt EMC box and obtained CE approval.
K30 Series Protection Relay Test Set
  •  Adopt advanced SCM as the control system which performs steadily and works immediately once the test set is started.
  • Scientific software organization mode and effective hardware guarantee to insure satisfied test effect.
  • Transient current response 20μs ; transient voltage 30μs.
  • Simultaneous output of voltage source (7 channels) and current source (6 channels) ; amplitude, phase and frequency adjustable independently; accuracy of output source adjustable by software;
  • Adopt the latest network technology to control by PC, widely applied;
  • Self-protection functions, such as voltage short circuit protection, current open circuit indication, and external input source induction alarm, etc;
  • Max. AC 300V per phase and provide independent Aux. DC source (0~300V adjustable);
  • Adopt EMC chassis and obtained CE approval.
K6 Series Protection Relay Test Set
  •  Satisfy the basic testing requirements of protection relay
  • 4 phase voltage source and 3 phase current source output simultaneous, amplitude value, phase and frequency adjustable.
  • Maximal AC voltage output per phase 300V, and supply individual AUX DC source.
  • All-in-one protection relay test set: built-in industrial personal computer, embedded Windows CE operation system, steady and reliable performance.
  • Adopt long life rotary encoder and button operation(built-in common shortcut key operation) to make the operation simply and conveniently.
  • Adopt EMC chassis and get CE certificate for complete appliance.
  • Have short circuit voltage protection, open circuit output current indicator, alarm for external input source connection etc protection functions.
  • Adopt 100M network card to transport data between computer and tester, at the same time the software of tester can be upgraded by USB, so the speed is improved greatly either report submission or software upgrade.
K511 Single-phase Relay Tester
  •  All-in-one design with local microprocessor controlled and LCD display ;
  •  Max.1300VA power output & 200A/300V AC output;
  •  300V Auxiliary DC with 0.5% accuracy;
  •  Meter input source testing of U,I,f,power and so on;
  • Matches different types of clamping meter to meet the requirement of testing the high current, max. 1000A
  •  Max.1024 testing result report local memory saving,display&analyze;
  •  Test settings storing and recalling from the local memory;
  •  Testable without PC&PC upgrading

For more Information please contact us on pdurandt@harmonious.co.za

Single Phase Protection Relay Test Set 
K511 K511 AC: 1 x 200A / 1 x300V / 1200VA
DC: 30A / 300V + AUX DC3 function modules, Ethernet, TFT LCD, WinCE
Production series of 3 phase to 6 phase relay test set
K50 Series(NEW) K5030 7 output channels      3x30A/4x130V
K5030i 7 output channels      3x30A/4x300V
K5063 10 output channels     6x20A/3x40A/4x130V
K5063i 10 output channels     6x30A/3x60A/4x300V
K5063S 10 output channels     6x15A, 4x300V
K5066 13 output channels     6x20A/3x40A/7x130V
K5066i 13 output channels     6x30A/3x60A/7x300V
K68 Series K68 3x35A, 4x130V, 5 function modules, Ethernet, TFT LCD, WinCE
K68i 3x35A, 4x300V, 5 function modules, Ethernet, TFT LCD, WinCE
K10 Series K1030 3x30A, 4x130V, 18 function modules Ethernet, TFT LCD, WinCE
K1030i 3x30A, 4x300V, 18 function modules Ethernet, TFT LCD, WinCE
K1063 6x20A, 4x130V, 18 function modules, Ethernet, TFT LCD, WinCE
K1063i 6x30A, 4x300V, 18 function modules, Ethernet, TFT LCD, WinCE
K1066 6x20A, 7x130V, 18 function modules, Ethernet, TFT LCD, WinCE
K1066i 6x30A, 7x300V, 18 function modules, Ethernet, TFT LCD, WinCE
K30 Series K3030 3x30A, 4x130V, 16 function modules, PC control
K3030i 3x30A, 4x300V, 16 function modules, PC control
K3063 6x20A, 4x130V, 16 function modules, PC control
K3066 6x20A, 7x130V, 16 function modules, PC control
K3066i 6x30A, 7x130V, 16 function modules, PC control